1.0 GENERAL
1.1 WORK INCLUDED
Provide liquid immersed, self cooled, pad-mounted transformer(s) in accordance with the following specifications.
1.2 STANDARDS
The low voltage on the right is to be provided with molded epoxy spade terminals with NEMA hole spacing. The installing contractor shall be responsible for providing suitable cable terminations.
Two (2) ANSI two-hole ground pads are to be provided on the base. A stainless steel connection diagram and nameplate shall be provided. The tap changing mechanism for de-energized operation shall be wall mounted in the primary compartment with external, padlockable operating handle.
3.3 Compartment sills, doors and covers shall be removable to facilitate cable pulling and installation. Compartments shall be designed for cable entry from below and shall be sized to the minimum dimensions of ANSI C57.12.26. The low voltage compartment shall include factory mounted 600 amp molded case breaker.
3.4 The transformer(s) is to be rated for continuous operation at full load at 65°C temperature rise with a 24 hour average ambient temperature of 30°C without loss of life expectancy. The transformer(s) and all current carrying parts shall also be designed to operate at 65°C.
3.5 The self cooled transformer(s) shall be designed with an average sound level not to exceed those defined in NEMA. This will be in accordance with the audible sound level test procedure as outlined in NEMA.
3.6 The transformer(s) shall be two winding type of circular coil construction using flat strip low voltage conductor and a round or rectangular high voltage conductor. All windings shall be of aluminum. The layer to layer insulation shall consist of thermally upgraded Shellac Craft diamond epoxy coated paper rated for operation at 65°C rise, 80°C hot spot.
3.7 The core shall be of the three legged stacked core design. High grade, grain oriented non-aging silicone coated core steel is to be utilized. Magnetic flux densities are to be kept well below saturation to allow for a minimum of 10% over voltage excitation.
3.8 The core frame shall be designed to provide maximum support of the core and coil assembly. The core frame shall be welded or bolted to ensure maximum short circuit strength. The core and coil assembly are to be designed and manufactured to meet the short circuit requirements of ANSI C57.12.90.
3.9 The core and coils are to be baked at 250°F to dry the unit and thermally set the epoxy. A Dissipation Power Factor test is to be performed to insure that moisture content has been minimized. Immediately after the drying process the core and coils are to be tanked and placed under a full vacuum. After the unit has been under a full vacuum for several hours the unit is to be filled with the appropriate cooling medium.
3.10 Transformers supplied with "less flammable" liquids shall be designed and manufactured to meet the requirements of the UL classification for less flammable fluids per NEC 450-23.
3.11 The transformer(s) shall be of the sealed tank construction of A36 grade mild steel with sufficient strength to withstand a pressure of 7 psi without permanent distortion. The tank shall be designed to permit rolling or skidding in any direction. The cover shall be domed to shed water and is to be welded with a bolted and gasketed handhole. Transformers supplied with "less flammable " liquids, (high molecular weight hydrocarbon fluid or silicone) shall be manufactured to withstand 12 psig without rupture. The transformer shall remain sealed for a top oil temperature range of -5°C to +105°C. Flat cooling panels in a common header on the back, sides or front shall be provided when required.
3.12 The transformer(s) is to be shipped as a unit requiring only anchoring to the pad and termination of high and low voltage cables. The required amount of liquid is to be factory installed. Any contacts required by this specification are to be wired in rigid steel conduit or liquidtite to within 18" of the contact and to a terminal block mounted in the low voltage compartment on the steel divider.
3.13 The transformer manufacturer shall certify that the transformer(s) is Non-PCB, containing no detectable PCBs. Do not provide high flash point liquids including askarel, or other liquids including tetrachlorethylene, perchlorethylene, chlorine compounds, or halogenated compounds.
3.14 When high voltage taps are specified, full capacity taps shall be provided with a tap changing mechanism designed for de-energized operation. The padlockable tap changer operator shall be located within the primary compartment.
3.15 When a primary switch is required, as shown on the plans, the switch is to be oil immersed with hook stick operating handle located in the primary compartment. The two position, gang operated, spring-loaded toggle switch is to be rated 200 amp continuous and load break, 15 kV, 95 kV BIL, 10 kA symmetrical momentary and fault close.